Technical
Specifications
+FLEX
EPR / CSP COIL LEAD to BS 6195, TYPE 4, HOFR
Category ‘C’ Voltage Rating - 0.6 to 1kV (Standard Product) BACK<<
Nominal
Conductor Size
mm2
Nominal
Conductor Stranding
No./size
mm
Nominal
Conductor Diameter
mm
Maximum
Overall Diameter
mm
Insulation
Radial Thickness
mm
Approx.
Cable Weight
Kg
/ Km
Current
Ratings(1)
(Amps)
Number
of Cables
Single
(2)
Two (3)
Three (3)
Four (3)
1.5
30 / 0.25
1.6
5.2
1.4
30
30
27
24
22
2.5
50 / 0.25
2.0
5.6
1.4
41
41
37
33
30
4
56 / 0.30
2.6
6.3
1.4
66
55
50
45
40
6
84 / 0.30
3.6
7.5
1.5
93
72
64
58
52
10
80 / 0.40
4.6
8.5
1.5
136
98
88
80
71
16
126 / 0.40
5.7
9.6
1.5
200
133
119
107
96
25
196 / 0.40
7.1
11.4
1.6
300
182
161
142
127
35
276 / 0.40
8.5
12.8
1.6
406
228
200
175
157
50
396 / 0.40
10.3
14.3
1.7
573
275
242
212
190
70
360 / 0.50
12.4
17.2
1.8
793
353
310
270
242
95
475 / 0.50
14.5
19.7
2.0
1028
430
377
327
293
120
608 / 0.50
15.5
21.9
2.2
1285
500
437
379
339
150
756 / 0.50
18.0
24.1
2.3
1562
577
504
444
400
185
925 / 0.50
19.5
26.3
2.4
1914
661
575
510
460
240
1221
/ 0.50
23.0
29.3
2.4
2431
781
679
607
547
300
1525
/ 0.50
26.0
33.0
2.6
3024
902
783
703
632
400
2013
/ 0.50
30.0
37.4
2.8
3948
1085
940
823
740
NOTES
The shaded area refers to standard stock cables.
(1) Ambient Air Temperature of 30 degrees celsius. Conductor operating
temperature of 90 degrees celcius.
(2) Continuous Current Rating (100% load factor) in Free Air.
(3) Continuous Current Rating (100% load factor), Bunched.